MODBUS_V2_Technical_Reference_Manual_APP2.0_01-2020.pdf
<aside> 💡 Applicable for APP versions >= 2.0.1
</aside>
Register | Size (bytes) | Base | Description | Default Value | Range (Min-Max) | Comments |
---|---|---|---|---|---|---|
304 | 2 | 10 | PIN code | |||
0 | ||||||
(deactivated) |
0 - 9999 | PIN code used with ATPIN command. Value 0 disables the PIN code. | | 306 | 1 | 10 | Product mode |  0 | 0: PARK 1: PRODUCTION | In PARK mode, product is not using Radio. In PRODUCTION mode, product will send/receive RF uplinks/downlinks. | | 308 | 4 | 16 | LED activity |  0x0018007F |  0 … 0xFFFFFFFF | Default: 18007F Eco : 180070 Other values : reserved |
Register | Size (bytes) | Base | Description | Default value | Min- Max Value | Comments |
---|---|---|---|---|---|---|
300 | 2 | 10 | Keep alive period | |||
8640 (24h) | 2 ... | |||||
65535 | ||||||
X 10 seconds | ||||||
301 | 2 | 10 | Transmit period for periodic data frame 1 | |||
8640 (24h) | 0 ... | |||||
65535 | x 10 seconds | |||||
0: deactivated | ||||||
320 | 2 | 10 | Sampling period for alarms | 180 | ||
(30 min) | 1 ... | |||||
65535 | ||||||
X 10 seconds | ||||||
321 | 1 | 16 | Modbus link configuration |
0x44 (19200/E/1 RS485) |         0 … 0xFF | Bit 0: Bus type •  0: RS485 •  1: RS232 Bit 1: Stop bits •  0: 1 bit •  1: 2 bits Bits 2 and 3: Parity •  0: None •  1: Even •  2: Odd Bits 4 to 7: Baud rate •  0: 1200 •  1: 2400 •  2: 4800 •  3: 9600 •  4: 19200 •  5: 38400 •  6: 57600 •  7: 115200 |
| 322 | 2 | 10 | Supply time of the external load (slave) before theModbus request | 0 (OFF) | 0 …65535 | x 100ms
•  0: no power supply (toward the slave)> •  From 1 to 65535: supply time of the external load (slave) before the Modbus request x100ms •  65535: permanent external power supply to the slave
E.g.: if S322 is set to 250, the power supply will be delivered to the slave 250x100ms ie 25s before the transmission of the Modbus request to the slave | | --- | --- | --- | --- | --- | --- | --- | | 323 | 2 | 10 | Transmit period for periodic data frame 2 | 8640(24 h) | 0 ...65535 | x 10 seconds0: deactivated | | 324 | 2 | 10 | Transmit period for periodic data frame 3 | 8640(24 h) | 0 ...65535 | x 10 seconds0: deactivated | | 325 | 2 | 10 | Transmit period for periodic data frame 4 | 8640(24 h) | 0 ...65535 | x 10 seconds0: deactivated | | 326 | 2 | 10 | Transmit period for periodic data frame 5 | 8640(24 h) | 0 ...65535 | x 10 seconds0: deactivated | | 327 | 2 | 10 | Transmit period for periodic data frame 6 | 8640(24 h) | 0 ...65535 | x 10 seconds0: deactivated | | 329 | 2 | 10 | Alarm repetition period | 0 | 0 ...65535 | x sampling period (S320) 0: no repetition |
Register | Size (bytes) | Base | Description | Default value | Min-Max value | Comments |
---|---|---|---|---|---|---|
330 | 4 | 16 | Periodic reading 1 | 0(deactivated) | 0 …0xFFFFFFFF | Bits 3 to 0: number of registers |
Bit 4: Modbus registers type | ||||||
• 0: holding registers (read/write) | ||||||
• 1: input registers (read only) | ||||||
Bits 7 to 5: Associated periodic frame | ||||||
• 0: periodic frame 1 | ||||||
• 1: periodic frame 2 | ||||||
• 2: periodic frame 3 | ||||||
• 3: periodic frame 4 | ||||||
• 4: periodic frame 5 | ||||||
• 5: periodic frame 6 | ||||||
Bits 23 to 8: First register address | ||||||
Bits 31 to 24: Slave address: | ||||||
• 0: data deactivated | ||||||
• 1 à 247: slave address | ||||||
331 | 4 | 16 | Periodic reading 2 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
332 | 4 | 16 | Periodic reading 3 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
333 | 4 | 16 | Periodic reading 4 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
334 | 4 | 16 | Periodic reading 5 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
335 | 4 | 16 | Periodic reading 6 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
336 | 4 | 16 | Periodic reading 7 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
337 | 4 | 16 | Periodic reading 8 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
338 | 4 | 16 | Periodic reading 9 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
339 | 4 | 16 | Periodic reading 10 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
340 | 4 | 16 | Periodic reading 11 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
341 | 4 | 16 | Periodic reading 12 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
342 | 4 | 16 | Periodic reading 13 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
343 | 4 | 16 | Periodic reading 14 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
344 | 4 | 16 | Periodic reading 15 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
345 | 4 | 16 | Periodic reading 16 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
346 | 4 | 16 | Periodic reading 17 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
347 | 4 | 16 | Periodic reading 18 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
348 | 4 | 16 | Periodic reading 19 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
349 | 4 | 16 | Periodic reading 20 | 0(deactivated) | 0 …0xFFFFFFFF | See register 330 |
Register | Size (bytes) | Base | Description | Default value | Min-Max value | Comments |
---|---|---|---|---|---|---|
350 | 4 | 16 | Alarm 1 configuration | 0(deactivated) | 0 …0xFFFFFFFF | Bits 1 to 0: Active thresholds • 1: Low threshold • 2: High threshold • 3: High and low thresholds Bit 2: Modbus register type • 0: holding registers (read/write) • 1: input registers (read only) Bit 3: Reserved Bits 4 and 6: Data type • 0: 16-bit unsigned integer • 1: 16-bit signed integer • 2: 32-bit unsigned integer • 3: 32-bit signed integer • 4: 32-bit unsigned integer (word swap) • 5: 32-bit signed integer (word swap) Bit 7: Reserved Bits 23 to 8: First register address Bits 31 to 24: Slave address: • 0: alarm deactivated • 1 à 247: slave address | | 351 | 2 | 16 | Alarm 1 - high threshold | 0 | 0 …0xFFFFFFFF | | | 352 | 4 | 16 | Alarm 1 - hysteresis of high threshold | 0 | 0 …0xFFFF | | | 353 | 2 | 16 | Alarm 1 - low threshold | 0 | 0 …0xFFFFFFFF | | | 354 | 4 | 16 | Alarm 1 - hysteresis of low threshold | 0 | 0 …0xFFFF | | | 355 - 359 | - | - | Alarm 2 configuration | - | - | See registers 350 to 354 | | 360 - 364 | - | - | Alarm 3 configuration | - | - | See registers 350 to 354 | | 365 - 369 | - | - | Alarm 4 configuration | - | - | See registers 350 to 354 | | 370 - 374 | - | - | Alarm 5 configuration | - | - | See registers 350 to 354 | | 375 - 379 | - | - | Alarm 6 configuration | - | - | See registers 350 to 354 | | 380 - 384 | - | - | Alarm 7 configuration | - | - | See registers 350 to 354 | | 385 - 389 | - | - | Alarm 8 configuration | - | - | See registers 350 to 354 | | 390 - 394 | - | - | Alarm 9 configuration | - | - | See registers 350 to 354 | | 395 - 399 | - | - | Alarm 10 configuration | - | - | See registers 350 to 354 |