| Register | Size (bytes) | Base | Description | Default Value | Range (Min- Max) | Comments |
|---|---|---|---|---|---|---|
| 304 | 2 | 10 | PIN code | 0 | ||
| (deactivate d) | ||||||
| 0 - 9999 | PIN code used with ATPIN command. Value 0 disables the PIN code. | |||||
| 306 | 1 | 10 | Product mode | |||
| 0 | 0: PARK | |||||
| 1: RUN | In PARK mode, product is not using Radio. In RUN mode, product will send/receive RF | |||||
| uplinks/downlinks. |
| Register | Size (bytes) | Base | Description | Default value | Min-Max Value | Comments |
|---|---|---|---|---|---|---|
| 300 | 2 | 10 | Keep alive period | 8640 (24h) | 2 ... 65535 | X 10 seconds |
| 301 | 2 | 10 | Transmit period of data for Delta Pressure |
1 | 0 ... 65535 | Number of backups (history logs) to be done before sending a frame (thus defining the sending period). The value 0 is equivalent to disabling the periodic mode. | | 308 | 4 | 16 | LED activity | 0x10007F | 0 … 0xFFFFFFFF | Default: 10007F Other values : reserved | | 320 | 2 | 10 | History period for Delta Pressure | 1 | 1 ... 65535 | Number of readings to be performed before saving in the history logs The value 1 is equivalent to 1 backup per reading | | 321 | 2 | 10 | Sampling period for Delta Pressure | 1800 (1h) | 0 ... 65535 | X 2 seconds 0 : no sampling (deactivation of the DELTA P function) | | 322 | 2 | 10 | History period for Analog channel | 0 | 1 ... 65535 | Number of readings to be performed before saving in the history logs The value 1 is equivalent to 1 backup per reading | | 323 | 2 | 10 | Sampling period for Analog channel | 0 (OFF) | 0 … 65535 | X 2 seconds 0 : no sampling (deactivation of the Analog function) | | 324 | 2 | 10 | Transmit period of data for Analog measures | 0 | 0 ... 65535 | Number of backups (history logs) to be done before sending a frame (thus defining the sending period). The value 0 is equivalent to disabling the periodic mode. |
| Register | Size (bytes) | Base | Description | Default value | Min-Max value | Comments |
|---|---|---|---|---|---|---|
| 330 | 1 | 10 | Alarm type for Delta Pressure | 0(inactive) | 0: Inactive | |
| 1: Low threshold | ||||||
| 2: High threshold | ||||||
| 3: Both thresholds | ||||||
| 331 | 2 | 10 | High threshold value (Delta P) | 0 | -500…500 | Value in Pa |
| 332 | 2 | 10 | High threshold hysteresis (Delta P) | 0 | 0…500 | Value in Pa |
| 333 | 2 | 10 | Low threshold value (Delta P) | 0 | -500…500 | Value in Pa |
| 334 | 2 | 10 | Low threshold hysteresis (Delta P) | 0 | 0…500 | Value in Pa |
| Register | Size (bytes) | Base | Description | Default value | Min-Max value | Comments |
|---|---|---|---|---|---|---|
| 350 | 1 | 10 | Alarm type (0-10V) | 0(inactive) | 0: Inactive | |
| 1: Low threshold | ||||||
| 2: High threshold | ||||||
| 3: Both thresholds | ||||||
| 351 | 2 | 10 | High threshold value (0-10V) | 0 | 0…10000 | Value in mV |
| 352 | 2 | 10 | High threshold hysteresis (0-10V) | 0 | 0…5000 | Value in mV |
| 353 | 2 | 10 | Low threshold value (0-10V) | 0 | 0…10000 | Value in mV |
| 354 | 2 | 10 | Low threshold hysteresis (0-10V) | 0 | 0…5000 | Value in mV |
| Register | Size (bytes) | Base | Description | Default value | Min-Max value | Comments |
|---|---|---|---|---|---|---|
| 380 | 1 | 16 | Digital Input/Output |
1
Configuration | 0x00 | <7:4> Debounce duration 0: no debounce 1: 10 ms 2: 20 ms 3: 50 ms 4: 100 ms 5: 200 ms 6: 500 ms 7: 1 s 8: 2 s 9: 5 s A: 10 s B: 20 s C: 40 s D: 60 s E: 5 minutes F: 10 minutes <3:0> Type 0 = Deactivated 1 = Event ON 2 = Event OFF 3 = Event ON/OFF 4 = Output | |
| 381 | 2 | 10 | Digital Input/Output 1 threshold | 1 | 1 – 65535 | Number of detections before to send the frame alarm |
|---|---|---|---|---|---|---|
| 382 | 1 | 16 | Digital input/output2 Configuration |
0x00 | <7:4> Debounce duration 0: no debounce 1: 10 ms 2: 20 ms 3: 50 ms 4: 100 ms 5: 200 ms 6: 500 ms 7: 1 s 8: 2 s 9: 5 s A: 10 s B: 20 s C: 40 s D: 60 s E: 5 minutes F: 10 minutes <3:0> Type 0 = Deactivated 1 = Event ON 2 = Event OFF 3 = Event ON/OFF 4=Output ON | | | 383 | 2 | 10 | Digital input/output 2 threshold | 1 | 1 – 65535 | Number of detections before to send the frame alarm | | 390 | 4 | 10 | Digital input 1 global counter | 0 | 0 – 232-1 | In-RAM counters that stores all the detected events on the channel
This register is not saved in EEPROM. Its value is therefore set to 0 if the product is not powered anymore | | 391 | 4 | 10 | Digital input 2 global counter | 0 | 0 – 232-1 | In-RAM counters that stores all the detected events on the channel
This register is not saved in EEPROM. Its value is therefore set to 0 if the product is not powered anymore | | 392 | 1 | 10 | Digital input 1 output state | 0 (OFF) | 0 (OFF / OPEN) – 1 (ON / CLOSED) | If channel is configured as an output, this register determines its state.
This register is not saved in EEPROM. Its value is therefore set to 0 if the product is not powered anymore | | 393 | 1 | 10 | Digital input 2 output state | 0 (OFF) | 0 (OFF / OPEN) – 1 (ON / CLOSED) | If channel is configured as an output, this register determines its state.
This register is not saved in EEPROM. Its value is therefore set to 0 if the product is not powered anymore |
| Register | Description | Encoding | Details |
|---|---|---|---|
| 201 | Spreading Factor (SF) by default (Read Only) | Decimal | Default: 12 |
| Min/max: 7 to 12 | |||
| Unit: None | |||
| 204 | Reserved | Hexadecimal | Do not use |
| 214 | LORA APP-EUI (first part – MSB) | Hexadecimal | Default: 0 |
| Key encoded on 16 characters. Each register contains a part of | |||
| the key. | |||
| Used during the JOIN phase in OTAA mode | |||
| E.g.: | |||
| APP-EUI = 0018B244 41524632 | |||
| • S214 = 0018B244 | |||
| • S215 = 41524632 | |||
| 215 | LORA APP-EUI (second part – MSB) | Hexadecimal | Default: 0 |
| Key encoded on 16 characters. Each register contains a part of | |||
| the key. | |||
| Used during the JOIN phase in OTAA mode | |||
| E.g.: | |||
| APP-EUI = 0018B244 41524632 | |||
| • S214 = 0018B244 | |||
| • S215 = 41524632 | |||
| 216 | LORA APP-KEY (firstpart – MSB) | Hexadecimal | Default: 0 |
| Key encoded on 32-byte characters. Each of the 4 registers contains 8 characters. | |||
| Used during the JOIN phase in OTAA mode | |||
| E.g.: | |||
| APP-KEY = 0018B244 41524632 0018B200 00000912 | |||
| • S216 = 0018B244 | |||
| • S217= 41524632 | |||
| • S218=0018B200 | |||
| • S219= 00000912 | |||
| 217 | LORA APP-KEY (second part – MID MSB) | Hexadecimal | Default: 0 |
| Key encoded on 32-byte characters. Each of the 4 registers contains 8 characters. | |||
| Used during the JOIN phase in OTAA mode | |||
| E.g.: | |||
| APP-KEY = 0018B244 41524632 0018B200 00000912 | |||
| • S216 = 0018B244 | |||
| • S217= 41524632 | |||
| • S218=0018B200 | |||
| • S219= 00000912 | |||
| 218 | LORA APP-KEY (thirdpart – MID LSB) | Hexadecimal | Default: 0 |
| Key encoded on 32-byte characters. Each of the 4 registers contains 8 characters. | |||
| Used during the JOIN phase in OTAA mode | |||
| E.g.: | |||
| APP-KEY = 0018B244 41524632 0018B200 00000912 | |||
| • S216 = 0018B244 | |||
| • S217= 41524632 | |||
| • S218=0018B200 | |||
| • S219= 00000912 | |||
| 219 | LORA APP-KEY (fourth part – LSB) | Hexadecimal | Default: 0 |
| Key encoded on 32-byte characters. Each of the 4 registers contains 8 characters. | |||
| Used during the JOIN phase in OTAA mode | |||
| E.g.: | |||
| APP-KEY = 0018B244 41524632 0018B200 00000912 | |||
| • S216 = 0018B244 | |||
| • S217= 41524632 | |||
| • S218=0018B200 | |||
| • S219= 00000912 | |||
| 220 | LoRaWAN Options | Hexadecimal | Default: 5 |
| Bit 0: Activation of the ADR ON(1)/OFF(0) | |||
| Bit 1: Reserved | |||
| Bit 2: DUTY CYCLE ON(1)/DUTY CYCLE OFF(0) | |||
| Bits 3 & 4: Reserved | |||
| Bits 5: CLASS C (1)/ CLASS A (0) | |||
| Bits 6 to 7: Reserved | |||
| CAUTION: | |||
| Deactivation of the Duty cycle may result in a violation of the | |||
| conditions of use of the frequency band, depending on the use of the device, thus violating the regulations in force. | |||
| In the case of disabling the Duty cycle, liability is transferred to | |||
| the user. | |||
| 221 | Mode of activation | Decimal | Default: 1 |
| Choice: (see NOTE 1 after the table) | |||
| • 0: ABP | |||
| • 1: OTAA | |||
| 222 | LORA NWK_SKEY (first part – MSB) | Hexadecimal | Default: 0 |
| Parameter encoded on 16 bytes. 4 registers contains 4 bytes. | |||
| 223 | LORA NWK_SKEY(second part - MID MSB) | Hexadecimal | |
| 224 | LORA NWK_SKEY (third part - MID LSB) | Hexadecimal | |
| 225 | LORA NWK_SKEY(fourth part – LSB) | Hexadecimal | |
| 226 | LORA APP_SKEY (first part – MSB) | Hexadecimal | Default: 0 |
| Parameter encoded on 16 bytes, each register with 4 bytes. | |||
| 227 | LORA APP_SKEY(second part - MID MSB) | Hexadecimal | |
| 228 | LORA APP_SKEY (third part - MID LSB) | Hexadecimal | |
| 229 | LORA APP_SKEY(fourth part – LSB) | Hexadecimal | |
| 280 | NETWORK ID | Hexadecimal | Default: 0 Read only |
| 281 | DEVICE ADDRESS | Hexadecimal | Default: 0 |
NOTE 1: The “Over The Air Activation” (OTAA) mode uses a JOIN phase before being able to transmit on the network. This mode uses the APP_ EUI (S214 and S215) and APP_KEY (S216 to S219) codes during this phase to create the keys for network communication.
Once this phase is completed, the codes APP_sKEY, NWK_sKEY and DEVICE ADDRESS will be present in the corresponding registers. A new JOIN phase is started every time the device exits Command mode, a reset is performed, or the device is turned on.
Codes:
The “Activation by personalization” (ABP) mode has no JOIN phase; it transmits directly on the network using the codes NWK_sKEY (S222 to S225), APP_sKEY (S226 to S229) and DEVICE ADDRESS (S281) to communicate.
Codes:
| --- | --- | --- | --- | --- | --- | --- | --- |