DOCUMENTATION GUIDE

TABLE OF CONTENTS

1. REGISTERS

1.1 Generic registers

Register Size (bytes) Base Description Default Value Range (Min-Max) Comments
304 2 10 PIN code 0
(deactivated)
0 – 9999 PIN code used with ATPIN command. Value 0 disables the PIN code.
306 1 10 Product mode
0 0: PARK
1: RUN In PARK mode, product is not using Radio.
In RUN mode, product will send/receive RF uplinks/downlinks.

1.2 Applicative registers

Register Size (bytes) Base Description Default value Min-Max Value Comments
300 2 10 Daily Frame
1 0: Disable
1: Daily transmission 1: Daily frame sent every 24H
301 2 10 Transmit period of data
2 → Sigfox 6 → LoRa

0 … 65535 | Number of backups (history logs) to be done before sending a frame (thus defining the sending period). The value 0 is equivalent to disabling the periodic mode. | | 308 | 4 | 16 | LED activity | 0x3E6006F | 0 … 0xFFFFFFFF | Default: 0x3E6006F Other values: reserved | | 315 | 1 | 10 | Time zone offset | 0 | -12 … 14 | Defines the Time Zone offset from UTC (in hours). Must be defined for Daylight Saving Time management. | | 316 | 1 | 10 | Daylight Saving Timemanagement | 0 | 0 … 1 | Only applicable for European countries. 0: disabled 1: enabled | | 318 | 1 | 10 | Time stamping |   0 |   0 … 1 | LoRaWAN only If enabled, adds a time stamp in data frames. 0: disabled 1: enabled | | 319 | 1 | 10 | RTCcalibration value | 0 | -100 … 100 | Allows correcting a possible drift of the clock. In tenths of a second per day. | | 320 | 2 | 10 | History period | 1 | 1 … 65535 | Number of readings to be performed before saving in the history logs. The value 1 is equivalent to 1 backup per reading | | 321 | 2 | 10 | Sampling period | 300 (10 min) | 15 … 65535 | 0: no sampling x2 seconds With S320 = 1 and S301 = 2 è 72 TX / Day With S320 = 1 and S301 = 6 è 24 TX / Day | | 322 | 2 | 10 | Alarm repetition period |   0 |   0 … 65535 | If an alarm is active, this register allows the product to send periodically a reminder.   0: no repetition X sampling period (S321) |

Register Size (bytes) Base Description Default value Min-Max Value Comments
323 1 10 Number of additional (redundant) samplesper frame 0

0 … 15 | Number of samples to be repeated in the next frame | | 324 | 1 | 10 | Black out duration | 0 | 0 – 12 (h) | 0 è blackout feature disable ≠ 0 è blackout active, duration of daily black out. Unit Hour | | 325 | 1 | 10 | Black out start time | 22 | 0 – 23 (h) | Black out start time. Unit Hour |

1.2.1 Black-out period

The device can daily suspend the sensor acquisition and associated processes, using the blackout parameters. When the blackout interval is entered:

When the blackout period is in progress:

Note: when the blackout is activated, the automatic calibration is not working.

1.2.2 CO2 Calibration registers

Register Size (bytes) Base Description Default Value Range (Min-Max) Minimum required Applicatio n version Comments
355 2 10
Calibration Reference Level 400

200-2000 |

= V2.3.0 | 0 ➔ Factory calibration [200-2000] ➔ use as target value when a calibration is performed | | S356 | 2 | 10 |   Automatic calibration period | 1 |   0-65534 |   = V2.3.0 | 0: Automatic calibration deactivated 1: Automatic calibration activated with default period of 180 hours 2-65534: Automatic calibration period in hours | | S357 | 1 | 10 | Start of the calibration by pressing the button | 1 |   0-1 |   = V2.3.2 | 0: Deactivated 1: Activated |

1.3 Alarm registers

1.3.1 Temperature

Register Size (bytes) Base Description Default value Min-Max value Comments
330 1 10 Alarm type 0 (inactive) 0: Inactive
1: Low threshold
2: High threshold
3: Both thresholds
331 2 10 High threshold value 0 -200 … 600
(-20°C to +60°C) tenth of °C
332 1 10 High threshold hysteresis 0 0…255 tenth of °C
333 2 10 Low threshold value 0 -200 … 600
(-20°C to +60°C) tenth of °C
334 1 10 Low threshold hysteresis 0 0… 255 tenth of °C

1.3.2 Humidity

Register Size (bytes) Base Description Default value Min-Max value
340 1 10 Alarm type 0 (inactive) 0: Inactive
1: Low threshold
2: High threshold
3: Both thresholds
341 1 10 High threshold value 0 0 … 100
342 1 10 High threshold hysteresis 0 0 … 255
343 1 10 Low threshold value 0 0 … 100
344 1 10 Low threshold hysteresis 0 0 … 255

1.3.3 CO2 alarm and QAI indicator

| --- | --- | --- | --- | --- | --- | --- |

Co2 alarm frame and CO2 “led” indicator are updated/evaluated each time a CO2 sensor measurement (sampling) is performed (according to S321 value, sampling period).

Note: CO2 LED indicator is not associated to an alarm frame.

These registers allow to update QAI led repetition period (i.e.: speeding up the led indication or decrease rate to optimize power consumption).

| --- | --- | --- | --- | --- | --- | --- |

1.4 Digital inputs

| --- | --- | --- | --- | --- | --- | --- |

1.5 Radio registers

1.5.1 LoRaWAN Network Registers

| --- | --- | --- | --- |

| --- | --- | --- | --- |

NOTE 1: The “Over The Air Activation” (OTAA) mode uses a JOIN phase before being able to transmit on the network. This mode uses the APP_ EUI (S214 and S215) and APP_KEY (S216 to S219) codes during this phase to create the keys for network communication. Once this phase is completed, the codes APP_sKEY, NWK_sKEY and DEVICE ADDRESS will be present in the corresponding registers. A new JOIN phase is started every time the device exits Command mode, a reset is performed, or the device is turned on.

Codes:

The “Activation by personalization” (ABP) mode has no JOIN phase; it transmits directly on the network using the codes NWK_sKEY (S222 to S225), APP_sKEY (S226 to S229) and DEVICE ADDRESS (S281) to communicate. Codes:

| --- | --- | --- | --- | --- | --- | --- | --- |