Register | Size (bytes) | Base | Description | Default Value | Range (Min-Max) | Comments |
---|---|---|---|---|---|---|
304 | 2 | 10 | PIN code | 0 | ||
(deactivated) | ||||||
0 – 9999 | PIN code used with ATPIN command. Value 0 disables the PIN code. | |||||
306 | 1 | 10 | Product mode | |||
0 | 0: PARK | |||||
1: RUN | In PARK mode, product is not using Radio. | |||||
In RUN mode, product will send/receive RF uplinks/downlinks. |
Register | Size (bytes) | Base | Description | Default value | Min-Max Value | Comments |
---|---|---|---|---|---|---|
300 | 2 | 10 | Daily Frame | |||
1 | 0: Disable | |||||
1: Daily transmission | 1: Daily frame sent every 24H | |||||
301 | 2 | 10 | Transmit period of data | |||
2 → Sigfox 6 → LoRa |
0 … 65535 | Number of backups (history logs) to be done before sending a frame (thus defining the sending period). The value 0 is equivalent to disabling the periodic mode. | | 308 | 4 | 16 | LED activity | 0x3E6006F | 0 … 0xFFFFFFFF | Default: 0x3E6006F Other values: reserved | | 315 | 1 | 10 | Time zone offset | 0 | -12 … 14 | Defines the Time Zone offset from UTC (in hours). Must be defined for Daylight Saving Time management. | | 316 | 1 | 10 | Daylight Saving Timemanagement | 0 | 0 … 1 | Only applicable for European countries. 0: disabled 1: enabled | | 318 | 1 | 10 | Time stamping |  0 |  0 … 1 | LoRaWAN only If enabled, adds a time stamp in data frames. 0: disabled 1: enabled | | 319 | 1 | 10 | RTCcalibration value | 0 | -100 … 100 | Allows correcting a possible drift of the clock. In tenths of a second per day. | | 320 | 2 | 10 | History period | 1 | 1 … 65535 | Number of readings to be performed before saving in the history logs. The value 1 is equivalent to 1 backup per reading | | 321 | 2 | 10 | Sampling period | 300 (10 min) | 15 … 65535 | 0: no sampling x2 seconds With S320 = 1 and S301 = 2 è 72 TX / Day With S320 = 1 and S301 = 6 è 24 TX / Day | | 322 | 2 | 10 | Alarm repetition period |  0 |  0 … 65535 | If an alarm is active, this register allows the product to send periodically a reminder.  0: no repetition X sampling period (S321) |
Register | Size (bytes) | Base | Description | Default value | Min-Max Value | Comments |
---|---|---|---|---|---|---|
323 | 1 | 10 | Number of additional (redundant) samplesper frame | 0 |
0 … 15 | Number of samples to be repeated in the next frame | | 324 | 1 | 10 | Black out duration | 0 | 0 – 12 (h) | 0 è blackout feature disable ≠0 è blackout active, duration of daily black out. Unit Hour | | 325 | 1 | 10 | Black out start time | 22 | 0 – 23 (h) | Black out start time. Unit Hour |
The device can daily suspend the sensor acquisition and associated processes, using the blackout parameters. When the blackout interval is entered:
When the blackout period is in progress:
Note: when the blackout is activated, the automatic calibration is not working.
Register | Size (bytes) | Base | Description | Default Value | Range (Min-Max) | Minimum required Applicatio n version | Comments |
---|---|---|---|---|---|---|---|
355 | 2 | 10 | |||||
Calibration Reference Level | 400 |
200-2000 |
= V2.3.0 | 0 âž” Factory calibration [200-2000] âž” use as target value when a calibration is performed | | S356 | 2 | 10 | Â Automatic calibration period | 1 | Â 0-65534 | Â = V2.3.0 | 0: Automatic calibration deactivated 1: Automatic calibration activated with default period of 180 hours 2-65534: Automatic calibration period in hours | | S357 | 1 | 10 | Start of the calibration by pressing the button | 1 | Â 0-1 | Â = V2.3.2 | 0: Deactivated 1: Activated |
Register | Size (bytes) | Base | Description | Default value | Min-Max value | Comments |
---|---|---|---|---|---|---|
330 | 1 | 10 | Alarm type | 0 (inactive) | 0: Inactive | |
1: Low threshold | ||||||
2: High threshold | ||||||
3: Both thresholds | ||||||
331 | 2 | 10 | High threshold value | 0 | -200 … 600 | |
(-20°C to +60°C) | tenth of °C | |||||
332 | 1 | 10 | High threshold hysteresis | 0 | 0…255 | tenth of °C |
333 | 2 | 10 | Low threshold value | 0 | -200 … 600 | |
(-20°C to +60°C) | tenth of °C | |||||
334 | 1 | 10 | Low threshold hysteresis | 0 | 0… 255 | tenth of °C |
Register | Size (bytes) | Base | Description | Default value | Min-Max value |
---|---|---|---|---|---|
340 | 1 | 10 | Alarm type | 0 (inactive) | 0: Inactive |
1: Low threshold | |||||
2: High threshold | |||||
3: Both thresholds | |||||
341 | 1 | 10 | High threshold value | 0 | 0 … 100 |
342 | 1 | 10 | High threshold hysteresis | 0 | 0 … 255 |
343 | 1 | 10 | Low threshold value | 0 | 0 … 100 |
344 | 1 | 10 | Low threshold hysteresis | 0 | 0 … 255 |
| --- | --- | --- | --- | --- | --- | --- |
Co2 alarm frame and CO2 “led” indicator are updated/evaluated each time a CO2 sensor measurement (sampling) is performed (according to S321 value, sampling period).
Note: CO2 LED indicator is not associated to an alarm frame.
These registers allow to update QAI led repetition period (i.e.: speeding up the led indication or decrease rate to optimize power consumption).
| --- | --- | --- | --- | --- | --- | --- |
| --- | --- | --- | --- | --- | --- | --- |
| --- | --- | --- | --- |
| --- | --- | --- | --- |
NOTE 1: The “Over The Air Activation” (OTAA) mode uses a JOIN phase before being able to transmit on the network. This mode uses the APP_ EUI (S214 and S215) and APP_KEY (S216 to S219) codes during this phase to create the keys for network communication. Once this phase is completed, the codes APP_sKEY, NWK_sKEY and DEVICE ADDRESS will be present in the corresponding registers. A new JOIN phase is started every time the device exits Command mode, a reset is performed, or the device is turned on.
Codes:
The “Activation by personalization” (ABP) mode has no JOIN phase; it transmits directly on the network using the codes NWK_sKEY (S222 to S225), APP_sKEY (S226 to S229) and DEVICE ADDRESS (S281) to communicate. Codes:
| --- | --- | --- | --- | --- | --- | --- | --- |